دراسة تجريبية لمبادل حراري صفائحي كمبرد هواء

محتوى المقالة الرئيسي

احمد أديب عبد الواحد

الملخص

As cooling air using water injection was limited by a range of humidity ratio so indirect humidification for air consider, this research take the study of heat transfer through a perpendicular plate heat exchanger to discover the influence optimum conditions on dehumidification efficiency and the amount of heat transfer energy across the plates of heat exchanger so calculating dehumidification efficiency and the amount of heat transfer energy across the plates of heat exchanger depending on the change of primary and secondary air flow rate using an experimental apparatus with an instruments for measuring air flow rate dry bulb temperature and wet bulb temperature on air entry and exit sections, experimental procedure by fixing primary air mass flow rate with changing secondary air mass flow rate once and the condition of entering primary air another time, also fixing secondary air mass flow rate with primary air mass flow rate once and the condition of entering primary ait another time Results show that the increasing of both the dehumidification efficiency and the amount of heat transfer energy across the plates of heat exchanger depend on the increasing of secondary and decreasing of primary air flow rate, percentage of increasing dehumidification efficiency 16 when secondary air mass flow rate increase from 0 to 0.2 kg's and percentage of increasing heat transfer 35 with above flow rate, percentage of decreasing dehumidification efficiency 12 when primary air mass flow rate increasing percentage 12 and percentage of increasing heat transfer 21 with above flow rate.

تفاصيل المقالة

كيفية الاقتباس
"دراسة تجريبية لمبادل حراري صفائحي كمبرد هواء" (2024) مجلة الهندسة, 16(04), ص 975–988. doi:10.31026/j.eng.2010.04.03.
القسم
Articles

كيفية الاقتباس

"دراسة تجريبية لمبادل حراري صفائحي كمبرد هواء" (2024) مجلة الهندسة, 16(04), ص 975–988. doi:10.31026/j.eng.2010.04.03.

تواريخ المنشور

المراجع

Davis Energy Group for California energy commission, " Indirect-Direct evaporative cooler (IDEC) Development Project Final report", 1995, P500.

Davis Energy Group for ACMA technologies Pte. Ltd, "Evaporative cooling market study , 2000, p27

Davis Energy Group for Heschong Mahone Group and the California energy commission, Advanced evaporative cooling white paper", 2002.

Davis Energy Group for California energy commission two-stage evaporative cooling system", 2004. pl. Development of an improved

Martin. "Heat exchangers", Hemisphere Publishing Corporation, 1992.

Paykoc, "Basic relationships for heat exchanger". Kluwer Academic Publishers, 1987, p29

Picon-Nunez, "Surface selection and design of plate-fin heat exchangers", 1999, p7

Saman "An experimental study of a cross-flow type plate heat exchanger for dehumidification/cooling". Solar Energy, 2002, p59

Saunders." Heat exchangers", John Wiley & Sons, 1988. p50.

Smith." Thermal design of heat exchangers", John Wiley & Sons, 1997.