OPEN CIRCUIT HEAT EXCHANGER DYNAMICS DURING FLOW REDUCTION TRANSIENT IN THEIR SECONDARY LOOPS

Main Article Content

Akram. W. Ezzat

Abstract

An experimental and theoretical analysis was conducted for simulation of open circuit cross flow heat
exchanger dynamics during flow reduction transient in their secondary loops. Finite difference
mathematical model was prepared to cover the heat transfer mechanism between the hot water in the
primary circuit and the cold water in the secondary circuit during transient course. This model takes under
consideration the effect of water heat up in the secondary circuit due to step reduction of its flow on the
physical and thermal properties linked to the parameters that are used for calculation of heat transfer
coefficients on both sides of their tubes. Computer program was prepared for calculation purposes which
cover all the variables that affect such type of transient mechanisms. The effect of the power density in
the primary circuit and the water flow reduction percentage on the average temperature build up of the
water in the primary circuit was investigated. The elapsed time required for the primary circuit average
temperature to reach a steady state value was also calculated. These calculations were supported with
experimental measurements conducted on a standard cross flow heat exchanger apparatus. The
experimental results were compared with the theoretical results for certain power density value at
different flow reduction percentages which show a reliable agreement. This relative agreement was
necessary to consider the mathematical model with certain assurance for calculating transient parameters
for higher power densities that are out of apparatus ranges. The results proved that water average
temperature build up in the primary circuit has sharp tendency when the percentage of flow reduction in
the secondary circuit reach 25% of its nominal values.

Article Details

How to Cite
“OPEN CIRCUIT HEAT EXCHANGER DYNAMICS DURING FLOW REDUCTION TRANSIENT IN THEIR SECONDARY LOOPS” (2011) Journal of Engineering, 17(06), pp. 1502–1516. doi:10.31026/j.eng.2011.06.16.
Section
Articles

How to Cite

“OPEN CIRCUIT HEAT EXCHANGER DYNAMICS DURING FLOW REDUCTION TRANSIENT IN THEIR SECONDARY LOOPS” (2011) Journal of Engineering, 17(06), pp. 1502–1516. doi:10.31026/j.eng.2011.06.16.

Publication Dates

References

Abdelfatah Lahzazi and Nicolas Galanis, Thermal transients in parallel flow heat exchanger research, Faculté de genie,

Université de Sherbrooke, 2000.

Christos Housiadas , Simulation of loss of flow transients in research reactors, Annals of Nuclear Energy, 27, 1683-1693, 2000.

EL-Wakel, M. M. , Nuclear Power Engineering, McGraw-Hill, New York, 1962.

Ezzat A. W. and Taki H. M., Final analysis report for IRT 5000 research nuclear reactor, 1987.

Gvozdenac D. D., Analytical solution for transient response of counter flow heat exchanger with finite wall capacitance,

Institute of Thermal Energy and Process Engineering, University of Novi Sad, 21000 Novi Sad, Yugoslavia, 1992.

Manish Mishra, P.K. Das and Sunil Sarangi , Transient behavior of cross flow heat exchangers due to perturbations in flow

and temperature, Department of Mechanical Engineering, Indian Institute of Technology, Kharagpur 721 302, India 2005.

M. Thirarimurugan, T. Kannadasan and E. Ramasamy, Simulation studies on a cross flow plate fin heat exchanger, American Journal of Applied Sciences 5 (10): 1318-1321, 2008.

N. Srihari, B. Prabhakara Rao, Bengt Sunden and Sarit K. Das, Transient response of plate heat exchangers considering effect of flow mal distribution, department of Mechanical Engineering, Indian Institute of Technology, 2004.

PRODIT, Heat exchangers test unit with water / water cross flow shell and tube heat exchanger exercise book, Reference 28301, Torinto, Italy.

Similar Articles