The regeneration of spent transformer oil taken from Al-Dora power station was studied. The regeneration process includes settling, filtration, thermo vacuum evaporation, and clay treatment. The settling was done by gravity to remove the mechanical particles. The filtration was done by filter paper [whatman quality! and 18.5 cm diameter). Thermo vacuum evaporation at 175°C and 241 mm Hg was used for removing the dissolved water and light petroleum impurities. The clay treatment was used for final improvement of transformer oil properties. Iraqi clay. Algerian clay and zeolite (A) were used and the results were compared. It was studied the effect of clay to oil ratio and the mixing time on the water content, break down voltage and the acidity. It was considered that the best operation conditions are clay to oil ratio 2/100, and time 5 min. In these conditions the oil has water content 32 ppm, break down voltage 55 kV and acidity 0.028 mg KOH/g oil. It was found that Algerian clay gives better improvement than zeolite and Iraqi elay using the same operating conditions. Langmuir. Freundlich, and the combination of them adsorption isotherms were studied in this investigation and it was found that Freundlich adsorption isotherm well represented the adsorption of water on clay comparing with others isotherms.

Article Details

How to Cite
“REGENERATION OF SPENT TRANSFORMER OIL” (2024) Journal of Engineering, 16(04), pp. 5799–5810. doi:10.31026/j.eng.2010.04.08.
Section
Articles

How to Cite

“REGENERATION OF SPENT TRANSFORMER OIL” (2024) Journal of Engineering, 16(04), pp. 5799–5810. doi:10.31026/j.eng.2010.04.08.

Publication Dates

References

Eklund, M., Sweden 2006, "Mineral Insulating Oils; Functional Requirements Specifications and Production", Nynas Naphthenics ABSE-149 82 Nynashamn, IEEE International Symposium on Electrical Insulation, 68-72.

Hodgson, P., "Transformer Oil Processing", Redragon Oil & Gas Systems International Inc., Cambridge, Ontario, Canada www.redragon.com.

Luki'c, J., Orlovic, A., Spiteller, M., Jovanovic, J., Skala, D., 2006, "Re-refining of waste mineral insulating oil by extraction with N-methyl-2-pyrrolidone", Separation and Purification Technology, 51, 150-156.

Regional Activity Centre for Cleaner Production (RAC/CP), 2000, "Recycling Possibilities and potential uses of used oils".

Basel convention technical guidelines on used oil re-refining or other re-uses of previously used oil no. 5. prepared by the technical working group of the basel convention and adopted by the third meeting of the conference of the parties to the basel convention in September 1995, Geneva.

Zakharich, M., Zaitsev, I., Komar, V.. Skornyakov, 1., 2001, "Analysis of Applied Spectroscopy, Vol. 68. No posto Nikonovich, F. Ryzhkov, M. and oil using IR analyzers", Journal of

Groves, M., 1990, Maintenance Of Liquid insulation", power system maintenance manual, western.

Lansdown. A., 1982, "Lubrication" first editon, Programon Press.

Similar Articles

You may also start an advanced similarity search for this article.