Experimental Study of the effect of closed cavity wall on buildings cooling loads saving

محتوى المقالة الرئيسي

Qussai Jihad Abdul Ghafour, Ass. Prof. Dr.
Bashar Kamil Mahmoud

الملخص

The experimental study showed the use of closed cavity wall (the thickness of the cavity 5cm) made a percentage reduction in the cooling load caused by heat gain from the wall by (21.5 %) compared with the conventional wall. also the thermal resistance of the closed cavity was an average (0.2 m2.oC/W).


The experimental results of the study showed that the use of closed cavity wall reduced the average temperature of the inner surface of the wall during the day, and that the reduction was an average (0.45 oC)  when compared with the conventional wall , as well as the use of closed cavity wall reduced the temperature difference range of the inner surface of the wall during the day, and that the reduction was an average (0.66 oC) when compared with the conventional wall .


 