Performance Evaluation of Small Scale Air-Conditioning System Using R22 and Alternative Refrigerants

Main Article Content

Khalid Ahmed Al-Joudi
Qusay Rasheed Abd Al-Amir

Abstract

A mathematical model has been formulated to predict the influence of high outdoor air temperature on the performance of small scale air - conditioning system using R22 and alternative refrigerants R290, R407C, R410A. All refrigerants were investigated in the cooling mode operation. The mathematical model results have been validated with experimental data extracted from split type air conditioner of 2 TR capacity. This entailed the construction of an experimental test rig which consists of four main parts. They are, the refrigeration system, psychrometric test facility, measuring instrumentation, and auxiliary systems. The conditioned air was maintained at 25 0C dry bulb and 19 0C wet bulb for all tests. The outdoor ambient air temperature was varied from 35 0C to 55 0C in 5 0C increments. The study showed that R290 is the better replacement for R22 when the air conditioning system works under high ambient temperature. It has better performance as a drop in refrigerant. R407C has the closest performance to R22, followed by R410A.

Article Details

How to Cite
“Performance Evaluation of Small Scale Air-Conditioning System Using R22 and Alternative Refrigerants” (2014) Journal of Engineering, 20(01), pp. 62–77. doi:10.31026/j.eng.2014.01.06.
Section
Articles

How to Cite

“Performance Evaluation of Small Scale Air-Conditioning System Using R22 and Alternative Refrigerants” (2014) Journal of Engineering, 20(01), pp. 62–77. doi:10.31026/j.eng.2014.01.06.

Publication Dates

References

Al-Amir Q. R., 2013," Experimental assessment and numerical simulation of the performance of small scale air-conditioning systems using alternative refrigerants to R-22" University of Baghdad, PhD thesis.

ASHRAE. 2009, ANSI/ASHRAE 37-2009," Methods of Testing for Rating Electrically Driven Unitary Air Conditioning and Heat Pump Equipment", American Society of Heating, Refrigeration, and Air-Conditioning Engineers, Inc.

ASHRAE Handbook of Fundamental, 2010, American society for Heating, Refrigeration and Air Conditioning Engineers, Inc., New York, Chapter 6.

Blanco D., Nagano K., Morimoto M., 2012" Steady state vapor compression refrigeration cycle simulation for a monovalent inverter-driven water-to-water heat pump with a desuperheater for low energy houses" International journal of refrigeration, 35, 1833- 1847.

Briggs, D.E. and Yong, 1962," Convection heat transfer and pressure drop of air flowing across triangular pitch banks of finned tubes",5th AICHE/ASME.

Cabello R., Navarro J., Torrella E., 2005, " Simplified steady-state modelling of a single stage vapor

compression plant. Model development and validation" Applied Thermal Engineering 25, 1740–1752.

Chang Y., Wang C., 1997, “A Generalized Heat Transfer Correlation for Louver Fin Geometry”, International Journal of Heat and Mass Transfer, Vol.40, pp. 533- 544.

Chen W., 2008," A comparative study on the performance and environmental characteristics of R-410A and R-22 residential air conditioners", Applied Thermal Engineering , Vol. 28, 1-7.

Cho I. S and Jung J.Y., 2010," Lubrication characteristics of a rotary compressor used for refrigeration and air-conditioning systems ", Journal of Mechanical Science and Technology 24 (4), 851-856.

Ding G., Hu H., Huang X., Deng B., Gao Y., 2009," Experimental investigation and correlation of two-phase frictional pressure drop of R410A–oil mixture flow boiling in a 5mm micro fin tube" International Journal of Refrigeration. 32, ,150 –161.

Ding G.L., Zhang C.L., 2001, "Simulation and Optimization of Refrigeration and Air Conditioning Appliances, Science Press, Beijing. Quoted by Zhou (2010).

Domanski, P.A., and David A. D., 1985," Simulation of a Heat Pump Operating with a Non azeotropic Mixture, ASHRAE Technical Data Bulletin" Advances in Non azeotropic Mixture Refrigerants for Heat Pumps, Vol.1, No.9, pp. 81, ASHRAE, Inc., Atlanta, GA.

Domanski P. A., Yashar D., Kim M., 2005, " Performance of a finned-tube evaporator optimized for different refrigerants and its effect on system efficiency ", International Journal of Refrigeration 28, 820–827.

Duprez, M.E., Dumont E., Frere M., 2007," Modeling of reciprocating and scroll compressors", International Journal of Refrigeration, 30, 5, 873-886.

Fisher S.K., Rice C.K., 1983, "A steady-state computer design model for air to air heat pumps", Oak Ridge National Laboratory, Oak Ridge, Tennessee, U.S.A.

Harms T. M., Braun J. E., and Groll E. A.,2002 "The Impact Of Modeling Complexity And Two-Phase Flow Parameters On The Accuracy Of System Modeling For Unitary Air Conditioners" , International Refrigeration and Air Conditioning Conference. Paper 569.

Incropera F., DeWitt D., 1990, "Fundamentals of Heat and Mass Transfer", third ed., John Wiley & Sons Inc., New Jersey, USA.

Jin H., and Spitler J.D., 2002. "A Parameter Estimation Based Model of Water-To-Water Heat Pumps for use in Energy Calculation Programs", ASHRAE Transactions, 108(1), pp. 3-17.

خالد احمد الجودي، 1991 . مبادئ هندسة تكييف الهواء و التثليج، الطبعة

الثانية، كلية الهندسة،جامعة البصرة.

Kim M.H., Bullard C.W., 2001, " A Simple Approach to Performance Analysis of Alternative Refrigerant Rolling Piston Type Rotary Compressors", MSc thesis, University of Illinois at Urbana Champaign.

Klein S.A., 2006, Engineering Equation Solver commercial version V8.914 .

McQuiston F. C., 1981, "Finned tube heat exchangers: state of the art for the air side", ASHRAE Trans., Vol.87, Part1, 1077-1085.

McQuiston F. C., Tree D. R., 1973, "Optimum space envelopes of the finned tube heat transfer surface," ASHAE Transactions, Vol.79, Pt. 2.

Munson B. R., Young D. F., 2010, " Fundamentals of Fluid Mechanics" Fourth edition, John Wiley & Sons. Inc. USA.

Rice C.K., Fisher S.K., Jackson W.L., Ellison R.D.,1981, "Design optimization and the limits of steady state heating efficiency for conventional single speed air source heat pumps", Oak Ridge National Laboratory, Oak Ridge, Tennessee ,U.S.A.

Richardson D. H., Aute V., Winkler J., and Radermacher, R. , 2004, " Numerical Challenges in Simulation of a Generalized Vapor Compression Refrigeration System." 2004 International Refrigeration and Air Conditioning Conference. Purdue University.

Sakaino K., Muramastsu S., Shida S., Ohinata O., 1984, " Some Approaches Towards a High Efficient Rotary Compressor, " International Compressor Engineering Conference, Purdue University.

Shah MM. , 1979, "A general correlation for heat transfer during lm condensation inside pipes". International Journal Heat and Mass Transfer, 22:547-56.

Sinpiboon J. , Wongwises S., 2002," Numerical investigation of refrigerant flow through non-adiabatic capillary tubes" Applied Thermal Engineering , 22, 2015–2032.

Spatz M. W., 2004, "Replacement for HCFC-22 in air conditioning and heat pump system".

Sukkarin C., Somchai W., 2011," A comparison of flow characteristics of refrigerants flowing through adiabatic straight and helical capillary tubes" International Communications in Heat and Mass Transfer 38, 398–404.

Techarungpaisan P., Theerakulpisut S., Priprem S., 2007, "Modeling of a split type air conditioner with integrated water heater", Energy Conversion Management, 48, 1222-1237.

Wakabayashi H., Yuuda J., Aizawa T., Yamamura M., 1982," Analysis of Performance in a Rotary Compressor" International Compressor Engineering Conference, Paper 385.

Wang S. K. , 2000, " Handbook of air conditioning and refrigeration" Second Edition, chapter 10 page 26.

Winandy E., Saavedra O. C. , Lebrun J., 2002, "Simplified modelling of an open-type reciprocating compressor" Int. J. Therm. Sci. 41, 183–192.

Winkler J. M. ,2009," Development of a component based simulation tool for the steady state and transient analysis of vapor compression systems", PhD Thesis, University of Maryland, College Park

Similar Articles

You may also start an advanced similarity search for this article.