Performance Analyses of 15 kW Grid-Tied Photo Voltaic Solar System Type under Baghdad city climate

Main Article Content

Nibras Mahmood Obaid
Emad T. Hashim
Naseer K. Kasim

Abstract

The performance analyses of 15 kWp (kW peak) Grid -Tied solar PV system (that considered first of its type) implemented at the Training and Energy Research Center Subsidiary of Iraqi Ministry of Electricity in Baghdad city has been achieved. The system consists of 72 modules arranged in 6 strings were each string contains 12 modules connected in series to increase the voltage output while these strings connected in parallel to increase the current output. According to the observed duration, the reference daily yields, array daily yields and final daily yields of this system were (5.9, 4.56, 4.4) kWh/kWp/day respectively. The energy yield was 1585 kWh/kWp/year while the annual total solar irradiation received by solar array system was 1986.4kWh/m2. The average power losses per day of array, system losses and overall losses were (1.38, 0.15, 1.53) kWh/kWp/day respectively. The average capacity factor and performance ratio per year were 18.4% and 75.5% respectively. These results highlighted the performance analyses of this PV solar system located in Baghdad city. The performance can be considered as good and significant comparing with other world PV solar stations.


 

Article Details

How to Cite
“Performance Analyses of 15 kW Grid-Tied Photo Voltaic Solar System Type under Baghdad city climate” (2020) Journal of Engineering, 26(4), pp. 21–32. doi:10.31026/j.eng.2020.04.02.
Section
Articles

How to Cite

“Performance Analyses of 15 kW Grid-Tied Photo Voltaic Solar System Type under Baghdad city climate” (2020) Journal of Engineering, 26(4), pp. 21–32. doi:10.31026/j.eng.2020.04.02.

Publication Dates

Similar Articles

You may also start an advanced similarity search for this article.