An Investigation into Thermal Performance of Mist Water System and The Related Consumption Energy

Main Article Content

Najim Abid Jassim
Firas Adel Abdulkareem Haris

Abstract

Experimental tests were conducted to investigate the thermal performance (cooling effect) of water mist system consisting of 5μm volume median diameter droplets in reducing the heat gain entering a room through the roof and the west wall by reducing the outside surface temperature due to the evaporative cooling effect during the hot dry summer of Baghdad/Iraq. The test period
was Fifty one days during the months May, June, and July 2012. The single test day consists of 16 test hours starting from 8:00 am to 12:00 pm. The results showed a reduction range of 1.71 to 15.5℃ of the roof outside surface temperature and 21.3 to 76.6% reduction in the daily heat flux entering the room through the roof compared with the case of not using water mist system. Also the results show a reduction range of 1.3 to 18.8℃ in the wall outside surface temperature. Finally numerical simulation with ANSYS-FLUENT.14 was conducted to compare its results with the experimental results of the roof and wall tests.

Article Details

How to Cite
“An Investigation into Thermal Performance of Mist Water System and The Related Consumption Energy” (2014) Journal of Engineering, 20(09), pp. 108–119. doi:10.31026/j.eng.2014.09.08.
Section
Articles

How to Cite

“An Investigation into Thermal Performance of Mist Water System and The Related Consumption Energy” (2014) Journal of Engineering, 20(09), pp. 108–119. doi:10.31026/j.eng.2014.09.08.

Publication Dates

References

➢ ANSYS, Inc, April 2009, ANSYS FLUENT 12.0 Theory Guide.

➢ Carrasco, A., Pittard, R., Kondepudi, S. N., and Somasundaram, S. Mechanical Engineering Department, Texas A&M University, College Station,1987, Evaluation of a Direct Evaporation Roof-Spray Cooling System, Proceedings of the Fourth Symposium on Improving Building Systems in Hot and Humid Climates, Houston, TX, September 15-16, 1987.

➢ Daisuke Narumi, Kentaro Shigemitsu and Yoshiyuki Shimoda, Osaka University Suita City, Osaka Pref., Japan , 2007 , Effect of the Evaporative Cooling Techniques by Spraying Mist Water on Reducing Urban Heat Flux and Saving Energy in Apartment House, PLEA 2009 - 26th Conference on Passive and Low Energy Architecture, Quebec City, Canada, 22-24 June 2009.

➢ Houghten, F.C., Olsen, H.T. & Gutberlet, C., 1940, Summer Cooling Load as Affected by Heat Gain Through Dry Sprinkled and Water Covered Roofs, American Society of Heating and Ventilation, (ASHVE Transactions) Engineers Transcripts,June,1940, Vol. 46, pp. 231.

➢ Leonard R. Bachman AIA President Building Climate Interface , Inc. Houston, Texas, 1985 , Rain on the Roof-Evaporative Spray Roof Cooling, Proceedings of the Second Symposium on Improving Building Systems in Hot and Humid Climates, College Station, TX, September 24-26, 1985.

➢ National Oceanic and Atmospheric Administration in the United State of America, http://www.ncdc.noaa.govhttp://www.ncdc.noaa.gov

Similar Articles

You may also start an advanced similarity search for this article.